Rockwell-automation 1769-IF4XOF2 Compact Combination Analog Module Uživatelský manuál Strana 19

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 24
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 18
Compact™ Combination Analog I/O Module 19
Publication 1769-IN057A-EN-P - July 2001
Specifications
General Specifications
Specification 1769-IF4XOF2
Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
290g (0.64 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G (when a relay module is used in the system)
Shock Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Bus Current Draw (max.) 120 mA at 5V dc
160 mA at 24V dc
Heat Dissipation 3.03 Total Watts (The Watts per point, plus the minimum Watts,
with all points energized.)
System Power Supply Distance Rating 8 (The module may not be more than 8 modules away from the
system power supply.)
Recommended Input/Output Cable Belden™ 8761 (shielded)
Max. Input/Output Cable Length 200m (656 feet) Exceeding cable length reduces accuracy. For
more information, see the Compact Combination Analog Module
User Manual, publication number 1769-UM008A-EN-P.
Module OK LED On: module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.
Field Calibration None required
Vendor I.D. Code 1
Product Type Code 10
Product Code 33
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE and C-Tick compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A