Compact Combination Fast Analog I/O Module 21
Publication 1769-IN081A-EN-P - February 2007
Process Alarm High Data Value Channel x = Provides the ability to configure
the Input Process Alarm High Value.
Process Alarm Low Data Value Channel x = Provides the ability to configure
the Input Process Alarm Low Value.
Alarm Dead Band Value Channel x = Provides the ability to configure the
Input Process Dead Band Value.
Reserved = Bits not used, must be set to 0.
EHI = Enable Output Channel Interrupt on High Clamp Alarm.
ELI = Enable Output Channel Interrupt on Low Clamp Alarm.
LC = Latch Low/High Clamp and Under/Over Range Alarm.
ER = Enable Ramping.
FM = Enable Fault Alternate Output State mode.
PM = Enable Program/Idle Alternate Output State mode.
PFE = Enable Program/Idle to Fault Alternate Output State mode.
Outpt Fm ChIx = Output Data Format Select.
Outpt Tp/Rnge Sel ChIx = Output Type/Range Select.
Ramp Rate Channel x = Provides the ability to configure the Ramp Rate.
Define To
Select
Make these bit settings
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Input Filter
Selection /
-3 dB
Frequency
60 Hz
0000
50 Hz
0001
5 Hz
0010
10 Hz
0011
100 Hz
0100
250 Hz
0101
500 Hz
0110
1000 Hz
0111
No
Filter
1000