Create Custom Web Pages 111
ACTION="/rokform/CIPMessage"
This method performs an instant CIP message request. The response
is an HTML stream.
The form accepts these parameters.
Input Description
Path Path to the data, such as “1,1”
Service Enter the CIP service name
Class Enter the class ID number
Instance
(optional)
Enter the instance number
Attribute
(optional)
Enter the attribute number
Member
(optional)
Enter the CIP member
Data
(optional)
Size of the data
Type Any of the following types: BOOL, SINT, INT, DINT, REAL or STRING
Connected
(optional)
For an unconnected request, enter one of the following:
FALSE,false,F,f,0,NO,no,OFF,off
For a connected request, enter one of the following:
TRUE,true,T,t,1,YES,yes,ON,on