12 MicroLogix 1762-OW8 Relay Output Module
Publication 1762-IN003B-EN-P - June 2013
Certifications
Certification (when product is
marked)
(1)
(1)
See product certification link at http://www.rockwellautomation.com/products/certification for Declaration of Conformity,
Certificates, and other certification details.
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S and Canada.
See UL File E334470.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Autralian Rediocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Output Specifications
Specification Value
Voltage category AC/DC normally open relay
Operating voltage range 5…265V AC
5…125V DC
Number of outputs 8
Bus current draw (max.) 80 mA @ 5V DC (0.40W)
90 mA @ 24V DC (2.16W)
Heat dissipation (max.) 2.9 Total Watts
Signal delay (max.) – resistive load On Delay: 10 ms
Off Delay: 10 ms
Off-state leakage (max.) 0 mA
On-state current (min.) 10 mA @ 5V DC
Continuous current per point (max.) 2.5 A (See “Relay Contact Ratings” on page 13.)
Continuous current per common
(max.)
8 A
Continuous current per module (max.) 16 A