Solid State 24V DC Source Output Module 9
Publication 1762-IN011B-EN-P - June 2013
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped end of the wire or a
spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire. Recommended
torque when tightening terminal screws is 0.90 Nm
(8 lb-in.).
Miswiring of the module to an AC power source will damage the module.
Finger-safe cover not shown for clarity.
If you need to remove the finger-safe cover, insert a screw driver into one of
the square wiring holes and gently pry the cover off. If you wire the
terminal block with the finger-safe cover removed, you will not be able to
put it back on the terminal block because the wires will be in the way.