ProcessLogix Pulse Input Module 5
Publication 1757-IN900A-US-P - February 2000
 Access Control Builder.
 Add a new 1757-PIM from the library.
a. Open the Library and Project tree views.
b. In the Library tree view, click on the 1757-PIM icon and drag it to the
Project tree window.
 Right-click on the desired IOM instance on the Project tree window.
 Click on Configure Param. You see the Main, Module Configuration, Channel
Configuration, Status/Data and Server Parameters configuration tabs.
 Under the Main tab (see figure below), enter a Module Name that is more
meaningful to you than its default IOMxxx (xxx represents a pre-assigned
number).