Publication 1756-UM521C-EN-P - July 2004
D-12 Configuring the Ring Configuration
Configure Time Slave Chassis - End Node
You must complete the following tasks to configure the second Time Slave
chassis.
Create a New RSLogix 5000 Project
Add a SynchLink Module
Configure the SynchLink Module
Name the module
Choose a receive communications format
Choose a transmit communications format
Choose an electronic keying option
Set the RPI
Make the module the CST Time Master for the chassis
Download Configuration
Create a New RSLogix 5000 Project
1. Use the File menu to create a new project.
2. Name the controller.
Time Slave
Chassis
ControlNet SynchLink
42991
Choose a New project
from the File menu.
F. Click here to use the
new controller.
A. The controller is a 1756-L1.
B. The controller is named
Time_Slave_End_Node.
C. The controller is used in a
7-slot chassis.
D. The controllers slot location
is 0.
Zobrazit stránku 121