14 Rockwell Automation Publication ENET-UM003B-EN-P - September 2013
Chapter 1 Secure Communication Architecture
Performance
The basic communication capability of the module is the same as the
1756-EN2T module.
The module supports the same number of TCP and CIP connections as
the 1756-EN2T module (256 CIP connections and 128 TCP/IP
connections).
The module supports configuration of IPsec associations with as many as
8 IP addresses (devices); only 1 of which can be a Cisco ASA connection.
The module supports CIP Sync communication.
Traffic Filtering
When IPsec is enabled, the module blocks traffic that is not received via a VPN
client, another peer with an IPsec connection, or an appliance with an IPsec
connection, with these exceptions:
BOOTP/DHCP traffic (to let the module obtain an IP address)
HTTPS traffic (needed to configure the module)
CIP Sync packets (you have the option to disable CIP Sync)
Logix produced/consumed tags (the establishment of the
produced/consumed connection occurs over via IPsec)
1756 I/O connections in a remote chassis
If the 1756-EN2TSC module is the trusted slot for a ControlLogix chassis, the
following traffic to the controller must go through the 1756-EN2TSC module.
RSLinx® Classic traffic (such as Studio 5000™ and ControlFLASH
communication)
RSLinx Enterprise traffic (such as FactoryTalk View® SE and
FactoryTalk View ME communication)