150 Configure Output Behavior with RSLogix 5000 Version 16 and Earlier
7. In the CFM_GenericProfileExample project, copy the following data
tags located in the Controller Tag folder.
8. In the CFM_DEMO project, paste the copied data tags into the
Controller Tags folder by using the Edit Tags tab.
9. In the CFM_GenericProfileExample project, copy ladder logic rung 1
located in the Main Routine folder.
10. In the CFM_DEMO project, paste the copied rung into the Main
Routine folder.
11. Change the Local:5 tag references to correspond to the location of your
1756-CFM module in your chassis.
12. Accept the pasted rung.
13. Delete the empty rung.