12 GuardPLC Relay Output Module
Rockwell Automation Publication 1753-IN012C-EN-P - June 2010
Relay Outputs
Number of outputs 8 normally open contacts
Switching voltage ≥ 5V, ≤ 250V AC/250V DC
Switching current UL:
• 24V DC @ 1 A noninductive, external fusing adapted
• 250V AC @ 6 A general purpose
TÜV:
• 30V DC, 90 W (3.15 A) max, noninductive, external fusing adapted
• 70V DC, 22 W (0.315 A) max, noninductive, external fusing adapted
• 127V DC, 25 W (0.25 A) max, noninductive, external fusing adapted
• 250V DC, 40 W (0.16 A) max, noninductive, external fusing adapted
• 250V AC, 250 VA, cos ϕ ≥ 0.5 max
• 250V AC, 625 VA, cos ϕ ≥ 1.0 max
Turn-on time approx. 30 ms
Turn-off time approx. 10 ms
Bounce time approx. 15 ms
Service life, mechanical ≥10
6
switching cycles
Service life, electrical ≥2.5 x 10
5
switching cycles with resisitive full load and ≤ 0.1 switching cycles
per second
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
Technical Specifications - 1753-OW8