18 GuardPLC 1753-IF8XOF4 Analog I/O Module
Publication 1753-IN013A-EN-P - September 2005
Environmental Conditions
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
-40°C to +85°C (-40°F to +185°F) without backup battery
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0°C to +60°C (+32°F to +140°F)
Vibration IEC60068-2-6 (Test Fc, Operating): 1 g @ 10…150 Hz
Shock, Operating IEC60068-2-27 (Test Ea, Unpackaged Shock):15 g
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
10 to 95% non-condensing
Emissions Group 1, Class A
ESD Immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80% AM from 80 Hz to 2000 MHz
EFT/B Immunity IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge Transient Immunity IEC 61000-4-5:
±500V line-line (DM) and ±500 line-earth (CM) on DC power ports
±1 kV line-earth (CM) on shielded ports
±1 kV line-earth (CM) on communication ports
Conducted RF Immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz to 80 MHz
Enclosure Type Rating meets IP20
Mechanical Dimensions
Width 207 mm (8.16 in.) including housing screws
Height 114 mm (4.49 in.) including latch
Depth 97 mm (3.82 in.) including grounding bolt
Weight 0.95 kg (2.09 lb)