18 SLC 500 RTD/Resistance Input Module
Publication 1746-IN007C-EN-P - December 2002
Input Specifications
RTD Types platinum, nickel, nickel iron, copper
(For additional information on RTD types, see page 21.)
Temperature
Scale (Selectable)
°C or °F and 0.1°C or 0.1°F
Resistance Scale
(Selectable)
1 or 0.1 for all resistance ranges except for 150Ω; or 0.1 or 0.01 for 150
potentiometer.
Input Step
Response
Refer to the SLC 500™ RTD/Resistance Input Module User Manual, publication number
1747-UM003A.
Channel Turn-On
Time
Requires up to one module update time plus module calibration time.
Channel Turn-Off
Time
Requires up to one module update time.
Reconfiguration
Time
Requires up to one module update time plus module calibration time.
Channel Scan
Time (with lead
resistance)
28 Hz = 250 ms
50/60 Hz = 147 ms
800 Hz = 18 ms
6400 Hz = 10 ms
Channel Scan
Time (without lead
resistance)
28 Hz = 125 ms
50/60 Hz = 75 ms
800 Hz = 10 ms
6400 Hz = 6 ms
RTD Excitation
Current
RTD setting:
0.25 mA - Recommended for use with higher resistance ranges for both RTDs and direct
resistance inputs (1000 RTDs and 3000 resistance input). Refer to RTD manufacturer for
recommendations.
1.0 mA -Recommended to use for all other RTD and direct resistance inputs, except 1000
RTDs and 3000 resistance input ranges are limited. Refer to RTD manufacturer for
recommendations.