Publication 1734-UM003B-EN-P - August 2005
1-12 About the Modules
Store-Reset/Start
Output Control
To connect an output to a compare window, you could program the
module accordingly:
Tie Output 0 to Window 0
Program Window 0 ON Value to 2000
Program Window 0 OFF Value to 5000
ON-OFF Operation of Output 0
If the OFF value is greater than the ON value, the output turns ON at
2000 and OFF at 5000. If the ON value is greater than the OFF value,
the output turns OFF at 2000 and ON at 5000.
a
nd Reset to zero
Start Counting
Continue Counti
ng
S
tore Count,
O
utput turns ON at count value of 2000
Output turns OFF at count value of 50
00
Output remains energized for 3000 additional counts
E
ffect of ON-OFF Value on Output Operation
O
utput turns ON Output turns OFF
Output remains Energized
a
t count of 2000
for 3000 additional counts
at count of 5000
Turn Off Value > Turn On Value
Output turns OFF Output turns O
N
Output remains Deenergized
at count of 2000
for 3000 additional counts
at count of 500
0
Turn On Value > Turn Off Value