1734 POINT I/O Protected Output Module 11
Publication 1734-IN056H-EN-P - May 2013
Communicate with Your Module
I/O messages are sent to (consumed) and received from (produced) the POINT I/O
modules. These messages are mapped onto the processor’s memory.
The POINT I/O output module produces 1 Byte of input data (scanner Rx) (status). It
consumes 1 Byte of I/O data (scanner Tx).
Default Data Map for 1734-OB2E
76543210
Produces (scanner Rx) Not used Ch1 Ch0 Channel status
Where: 0 = No error, 1 = Error
Message size: 1 Byte
76543210
Consumes (scanner Tx) Not used Ch1 Ch0 Channel state
Where: 0 = Off, 1 = On
Default Data Map for 1734-OB4E
76543210
Produces (scanner Rx) Not used Ch3 Ch2 Ch1 Ch0 Channel status
Where: 0 = No error, 1 = Error
Message size: 1 Byte
76543210
Consumes (scanner Tx) Not used Ch3 Ch2 Ch1 Ch0 Channel state
Where: 0 = Off, 1 = On
Default Data Map for 1734-OB8E
76543210
Produces (scanner Rx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Channel status
Where: 0 = No error, 1 = Error
Message size: 1 Byte
76543210
Consumes (scanner Tx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Channel state
Where: 0 = Off, 1 = On