B-8 1734-ADNX Quick Start
If you are not going to use the subnet, you must still terminate it!
You can use the connector provided with the 1734-ADNX and
connect two resistors between the white and blue positions.
Termination resistors are 121 Ohms, 1/4 Watt, 1%, Rockwell
part number 1785A-C2.
Do not use carbon resistors. Metal film is recommended.
Continue ONLY after You have verified that the taps are
terminated correctly.
20. Double click on the 1734-ADNX to open the properties window.
In the next step you will download the EDS defaults to the
1734-ADNX.
21. Select the parameter tab and choose Download.