Rockwell-automation 1734-8CFGDLX POINT I/O Module with 8 Configurable Uživatelský manuál Strana 13

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 28
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 12
POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix 13
Publication
1734-IN039A-EN-P - March 2009
Configure the Module
Read this section for information about how to communicate with your
module.
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s or
scanner’s memory. Each module produces 1, 8 or 20 bytes of input data based
on which produced assembly is selected. The default setup is 20 bytes.
It consumes 1, 8 or 20 bytes of I/O data (scanner Tx).
Default Data Map - Produced Assembly Instance 101
Message Size: 20 Bytes
Bit 7 6 5 4 3 2 1 0
Data [0] Pt 07 Pt 06 Pt 05 Pt 04 Pt 03 Pt 02 Pt 01 Pt 00
Data [1] PNB 07 PNB 06 PNB 05 PNB 04 PNB 03 PNB 02 PNB 01 PNB 00
Data [2] Reserved Owned
LogicEn
Data [3] PM7 PM6 PM5 PM4 PM3 PM2 PM1 PM0
Data [4] Produce Network Analog Word 0
Data [5]
Data [6] Produce Network Analog Word 1
Data [7]
Data [8] Produce Network Analog Word 2
Data [9]
Data [10] Produce Network Analog Word 3
Data [11]
Data [12] Produce Network Analog Word 4
Data [13]
Data [14] Produce Network Analog Word 5
Data [15]