Rockwell Automation Publication 1608P-UM005A-EN-P - November 2014 9
Installation Chapter 2
Electrical Terminations
Use a qualified electrician to install the HC-DySC in compliance with all local,
and national electric codes. The HC-DySC input (line) and output (load)
terminals are located behind the left door. Terminal details are shown in Figure 5
on page 12.
Accessing Terminations
For top entry, remove the top gland plate, which is shown in Figure 2, to access
input and output terminals. This plate may be removed for drilling or punching
holes for conduit. Alternate bottom entry should utilize the bottom gland plate
shown in Figure 1
. Access to the communications port is above the front doors, as
shown in Figure 6 on page 13
. A separate conduit knock-out is provided for top
entry of communications conductors, as shown in Figure 2
.
Note: When punching or drilling holes for conduit fittings, take care to avoid
dropping metallic particles inside the enclosure. Metallic contamination voids
the product warranty.
Figure 2 - Top Conductor Entry
3.00
76
11.00
279
2.00
51
9.00
229
20.75
527
51.07
1297
Area
Recommended
For Top
Conduit Entry
(Shown Without
Cover)
I/O Knockouts
WARNING: Metallic Particles inside the Enclosure Void the Warranty