Parameters B-3
1503-UM054C-EN-P – June 2013
Table B.3 – Conversion Table
Binary Hex Binary Hex Binary Hex Binary Hex
Parameter Numbers The parameter number value, for each parameter type, lists 5 values
separated by commas. The description of these 5 values is as
follow s:
a, b, c, d, e
a = parameter number for a 5IB multi-contactor system
b = parameter number for a 4IB multi-contactor system
c = parameter number for a 3IB multi-contactor system
d = parameter number for a 2IB multi-contactor system
e = parameter number for a 1IB multi-contactor system
Depending on the multi-contactor system which is used, simply
select the value of the parameter number corresponding to the
appropriate system.
Control Parameters Auxiliary Input Status from IntelliVAC Base Unit #1
[IB 1 Module Aux. Status]
Parameter Number: 1,1,1,1,1.
Access rule: Get
Data Type: BOOL
Objec t Mapping: 0x384-1-1
Group: Control
Units : -
Minimum Value: 0 = Closed
Maximum Value: 1 = Open
Default Value: 0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #1. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers to
the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electric al Spec ific ations
section in Table 1.A for the voltage level for a valid Closed and
Open input.