5-4 Monitoring and Troubleshooting
1503-UM 052D-EN-P Ju ne 2013
Contactor Status (cont.)
Table 5.B IntelliVAC Status Indication (Series D only)
Conditions

Description
Module Status Contactor Status
LED Color
Relay
LED Color
Relay
Normal Healthy Module and Contactor OPEN Green Closed Off Open
Normal Healthy Module and Contactor CLOSED Green Closed Yellow Closed
Warning Invalid Command Present Yellow Closed Off Open
Warning Mechanical Latch Fail to Trip Yellow Closed Yellow Closed
Fault Power Up with Contactor CLOSED Red Flash 2 Open Yellow Closed
Warning Contactor Fails to Pick Up Yellow R1 Closed Off / Yellow Open/Closed
Warning Contactor Drop Out During Hold Yellow R2 Closed Off / Yellow Open/Closed
Warning Long Contactor Drop Out Time Yellow R3 Closed Off / Yellow Open/Closed
Fault Microcontroller Malfunction Red Open Red Open
Fault Power Up with Invalid Dip Switch Configuration
Red Flash 1
Open Off Open
Warning Undervoltage with a CLOSE Command Present Yellow Flashing Open/Closed Off / Yellow Open/Closed
Warnings will be cleared when a change of input state occurs, and the condition has been resolved.
Faults require control power to be removed until the unit resets
Flash 1 = 1 Flash Red LED followed by a pause
Flash 2 = 2 Consecutive Red LED flashes followed by a pause
Yellow R1 = Yellow with 1 Red flash followed by a pause
Yellow R2 = Yellow with 2 consecutive Red flashes followed by a pause
Yellow R3 = Yellow with 3 consecutive Red flashes followed by a pause
Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence
2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified).
Allow at least 60 msec, plus drop out delay time, before re-applying these signals.
NOTE: Contactor will only respond to a close command re-applications after the re-start delay timer has expired.
3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).
Open during undervoltage, Closed if voltage restored
Will reflect actual status of the contactor
Only for Electrically Held Contactor
Undervoltage conditions are defined on page 3-17.