Electrically Held to Mechanical Latch Contactor
Retrofit Instructions – Series E or later
Compatibility This procedure applies to kit 1502-4MLK, and it is for 400A OEM
Vacuum Contactors listed at Series E or greater. The series letter can
be verified from the contactor nameplate:
Figure 1 – Bulletin 1502 – 400A Contactor
In addition, ensure that the contactor molding has the three slotted
holes and one round hole to the right of the magnetic coils that are
required to mount latch mechanism and rubber stop.
This retrofit kit can only be applied to contactors using IntelliVAC
Control circuits:
Figure 2 – IntelliVAC Control Assembly