DeviceNet Cable System Layout for Medium Voltage Controller Structures 3-3
1500-IN057C-EN-P June 2013
Figure 3.2A Left Termination Resistor Figure 3.2B Right Termination Resistor
RED
WHITE
BLACK
BLUE
No Shield or bare wire
required in class 1
DeviceNet MCCs
Terminating resistor (part number 1485A-C2)
Five-terminal plug connector
Part # 22186-084-01 with jack screws (Left Side)
Part #22105-006-012 with jack screws (Right Side)
RED
WHITE
BLACK
BLUE
No Shield or bare wire
required in class 1
DeviceNet MCCs
Terminating resistor (part number 1485A-C2)
Five-terminal plug connector
Part # 22186-084-01 with jack screws (Left Side)
Part #22105-006-012 with jack screws (Right Side)
Figure 3.3 Five Terminal Plug Connector
When installing terminating resistors, apply the following two rules:
1. Use only two terminating resistors in any network
2. Install terminating resistors at the ends (communication and/or
physical) of the trunk line located in the overhead horizontal
wireway.
Incorrect placement of terminating resistors and/or using more than two
will cause improper network operation and result in communication
losses.
Installing Terminating
Resistors