40752-093(1) Effective 5/02DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN-TENANCE ON EQUIPMENT WHILE ENERGIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTAN-T
Page 10Fig. 4-3 Short Delay Trip Current and Short Delay Trip Time Adjustment and Curve Details for H Type Trip UnitFig. 4-4 Ground Fault Trip Unit C
Page 11Fig. 5-2 Connection Diagrams Ground Fault Breaker - Figure indicates normal feed installation. Neutral sensor is wired identically for reverse
Page 12SOME COMMERCIAL CLEANING AGENTS WILL DAMAGE THE NAMEPLATES OR MOLDED PARTS. MAKE SURE THAT CLEANING AGENTS OR SOL-VENTS USED TO CLEAN THE CIRCU
40752-093(1) Effective 5/02Page 137.3.4 Using a low voltage (0-24V), high current, AC source, apply a test current of 125% of the ground fault pick-up
40752-093(1) Effective 5/02Page 14Fig. 7-2 Typical Performance Test RecordGROUND FAULT TEST RECORD FORMGround Fault Test Record should be Retained by
40752-093(1) Effective 5/02Page 15NOTES
Page 1640752-093(1) Effective 5/02Printed in U.S.A./TQC
Page 2ature operating range. Consult Allen-Bradley for recom-mendations.Molded Case Switches: The Molded Case Switch is similar to the Circuit Breaker
Page 3➀ Not UL listed➁ Occurs with short delay time adjustment set at I.➂ The Molded Case Switch has a fixed non-interchangeable rating plugGround Fau
Page 4This instruction leaflet gives procedures for installation and field testing of N-frame circuit breakers and describes the different trip unit c
Page 5Fig. 2-1 Terminal InstallationFig. 2-2 Conductor Extensions and Terminal Installation for 100% RatingFor bus connections use:.500-13 bolts (Engl
Page 6Fig. 2-3 Breaker Mounting Bolt Drilling PlanFig. 2-4 Circuit Breaker Escutcheon DimensionFig. 2-5 Securement of Cable (See caution note for brac
Page 7Wrap conductor cables with 3/8” nylon or equivalent rope as shown in Fig. 2-5, having a minimum tensile strength of 2000 Ibs, at 6” from termina
Page 8Fig. 3-1 Circuit Breaker Manual Controls3.2 Circuit Breaker ResetAfter an automatic or accessory initiated trip, or a manual push-to-trip operat
40752-093(1) Effective 5/02Page 94.6 Ground Fault Pick-up SettingSix settings marked 1x through 6x IG (where IG = 200 Amps) are available (see Fig. 4-