10 Bulletin 1405 (M620) Operating Instructions
Analog outputs selected as ‘I’, ‘=’, ‘P’ or ‘S’ provide a linear
measurement scaled from zero to the full-scale value as configured by
the V
nominal
and I
nominal
settings.
Refer to Table 4 and Table 5 for more information.
With the output range set to 0 to 20 mA, the relationships are:
Table 4
Line-to-line voltages (V
L-L
)
for 0 to 20 mA Range
10 mA V V
nom
()1()4 10 mA+
Line-to-neutral voltages (V
L-N
)
for 0 to 20 mA Range
10 mA 3() VV
nom
()1()4 10 mA+
Currents
20 mA I I
nominal
Power (per phase)
20 mA PX V
nominal
3I
nominal
()
Total power
20 mA P V
nominal
I
nominal
3()
Power factor
10 mA 10 mA 1 Cos f()0.5 (capacitive()+
10 mA 10 mA 1 Cos f()0.5 (inductive()
With the output range set to 4 to 20 mA, the relationships are:
Table 5
Line-to-line voltages (V
L-L
)
4 mA 8 mA V V
nom
()1()48 mA++
Line-to-neutral voltages (V
L-N
)
4 mA 8 mA 3() VV
nom
()1()48 mA++
Currents
4 mA 16 mA I I
nominal
+
Power (per phase)
4 mA 16 mA PX V
nominal
3I
nominal
()+
Total power
20 mA P V
nominal
I
nominal
3()
Power factor
4 mA 8 mA 8 mA 1 Cos f()0.5 (capacitive)++
4 mA 8 mA 8 mA 1 Cos f()0.5 (inductive)+
Zobrazit stránku 9