ALLEN-BRADLEYInstallationand OperationManualLine SynchronizationModule(Bulletin 1402 LSM)Allen-Bradley

Strany 2 - • recognize the consequences

Chapter 1Product Description1–4

Strany 3 - Table of Contents

A–B2Chapter2–1InstallationThe Bulletin 1402 Line Synchronization Module (LSM) should be installedin a Bulletin 1771 I/O chassis that is located in a d

Strany 4

Chapter 2Installation2–2The LSM requires the use of a Cat. No. 1771-WC (10 position, goldcontacts) Swing Arm.There are two sets of terminals associate

Strany 5 - Using This Manual

Chapter 2Installation2–3For proper monitoring and synchronization, correct selection of currenttransformers (CT’s) and potential transformers (PT’s) i

Strany 6 - Terms and Conventions

Chapter 2Installation2–4Other factors may affect CT accuracy. The length of the CT cabling shouldbe minimized because long cabling could contribute to

Strany 7

Chapter 2Installation2–5Connection for Three Phase Delta, 3 Wire Systems with 3 PT’s & 3 CT’SWhen configured for ungrounded (floating) Delta opera

Strany 8 - • Synchronization Status

Chapter 2Installation2–6Current Transformer ConnectionsThe LSM is equipped with four CT inputs, designated I1 – I4. Inputs I1 – I3are used to measure

Strany 9 - Module Configuration

Chapter 2Installation2–7Figure 2.1 – Wiring Diagram for 4–Wire Wye ConnectionSynchronizing Bus VoltageL1 L2 L3 NCT Terminal Block12345678A0234571BRefe

Strany 10 - Product Description

Chapter 2Installation2–8Figure 2.2 – Wiring Diagram for 3–Wire Wye ConnectionSynchronizing Bus VoltageL1 L2 L3CT Terminal Block12345678A023451BReferen

Strany 11

Chapter 2Installation2–9Figure 2.3 – Wiring Diagram for 3 Transformer Delta ConnectionSynchronizing Bus VoltageL1 L2 L3CT Terminal Block12345678A02345

Strany 12 - Swing Arm

Solid state equipment has operational characteristics differing from those ofelectromechanical equipment. “Safety Guidelines for the Application,Insta

Strany 13 - Selection

Chapter 2Installation2–10Figure 2.4 – Wiring Diagram for 2 Transformer Open–Delta ConnectionSynchronizing Bus VoltageL1 L2 L3CT Terminal Block12345678

Strany 14 - Chapter 2

Chapter 2Installation2–11Figure 2.5 – Wiring Diagram for 2 Transformer Open–Delta Connection With 2 CT’sSynchronizing Bus VoltageL1 L2 L3CT Terminal B

Strany 15

Chapter 2Installation2–12

Strany 16 - Calibration

A–B3Chapter3–1General OperationThis chapter:• introduces the user to the controls and operation• describes each function• defines operating parameter

Strany 17 - Figure 2.1

Chapter 3General Operation3–2Voltage ModeThis entry is used to indicate if the system being monitored is wired in aWYE, a Delta, or an open Delta. A v

Strany 18 - Figure 2.2

Chapter 3General Operation3–3Phase Match Error Upper and Lower Acceptance LimitsThese entries are used to specify the upper and lower acceptance limit

Strany 19 - Figure 2.3

Chapter 3General Operation3–4Demand PeriodThis entry is used to specify the desired period for demand measurement.The value is specified in minutes an

Strany 20 - Figure 2.4

Chapter 3General Operation3–5Synchronization ContinuedThe “Permissive Synchronization” discrete output from the PLC–5 preventsthe LSM from issuing any

Strany 21 - Figure 2.5

Chapter 3General Operation3–6Power MonitoringIn addition to the synchronization function, the LSM provides an extensivearray of monitoring information

Strany 22

Chapter 3General Operation3–7Load SharingThe load sharing function allows multiple synchronizing buses to split theload requirements on a power system

Strany 23 - General Operation

Table of ContentsiProduct Description 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . Chapter Objectives 1–1. . . . . . . . . . . . . . . . . .

Strany 24 - Chapter 3

Chapter 3General Operation3–8ControlThe user can direct the LSM to perform several different functions bysending the appropriate block transfer data t

Strany 25

Chapter 3General Operation3–9Self–test ContinuedThe red Fault LED flashes while the complete self–test is being performed.The Fault LED will remain on

Strany 26

Chapter 3General Operation3–10Discrete Outputs (From the PLC Processor)The following discrete output control signals will be provided from thePLC–5 pr

Strany 27

Chapter 3General Operation3–11Configuration Software Support6200 SoftwareSetup assistance for the LSM module is provided through the 6200 version4.4 o

Strany 28

Chapter 3General Operation3–12

Strany 29

A–B4Chapter4–1Application InformationModes of OperationThe Line Synchronization Module (LSM) has several modes of operation.Upon successful configurat

Strany 30

Chapter 4Application Information4–2Synchronization and Monitor with Load ShareIn this mode of operation, data is returned for Synchronizing Bus voltag

Strany 31 - Discrete I/O Interface

Chapter 4Application Information4–3Block Transfer Communications ContinuedFor example, the words 10 modulus 103 and 0 modulus 100 would beprocessed in

Strany 32 - PLC Interface Continued

Chapter 4Application Information4–4Acquiring Data From the LSMThe data from the LSM is returned in four tables. These tables are againdifferentiated b

Strany 33

Chapter 4Application Information4–5Discrete Outputs From The PLC–5 Continued present, the synchronization fails and the “Synchronization Failure” disc

Strany 34

Table of ContentsiiPLC Interface 3–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Discrete I/O Interface 3–9. . . . . . . . . .

Strany 35 - Application Information

Chapter 4Application Information4–6Discrete Inputs to the PLC–5The discrete inputs to the PLC–5 are as follows:Table 4.3Octal BitNumberDecimal BitNumb

Strany 36 - Block Transfer Communications

Chapter 4Application Information4–7Discrete Inputs to the PLC–5 ContinuedThe Lower Speed – Frequency Adjust synchronization error discrete input tothe

Strany 37 - • modulus 10

Chapter 4Application Information4–8Discrete Inputs to the PLC–5 ContinuedThe Close Breaker discrete input to the PLC–5 indicates that allsynchronizati

Strany 38 - Chapter 4

Chapter 4Application Information4–9Data Files UsedTable 4.4Data File Data Descriptionb3/0 Internal Triggerb3/1 Config Mode Enableb3/2 Data Resetb3/3 R

Strany 39

Chapter 4Application Information4–10Data Files Used ContinuedThe following description applies to both files N21 and N22.The data at word 0 of N21 and

Strany 40

Chapter 4Application Information4–11Data Files Used ContinuedTable 4.5File DescriptionN30 Factory Configuration Parameters BTR DestinationN31 User Con

Strany 41

Chapter 4Application Information4–12

Strany 42

AAppendixA–1Catalog Number ExplanationLINE SYNCHRONIZATION MODULE1402 - LS 5 15 5A Full ScaleMeasuredCurrentType ofDeviceMeasuredPhaseVoltage1402Power

Strany 43 - Continued

Appendix ACatalog Number ExplanationA–2

Strany 44

A–BAppendixBB–1Block Transfer and Discrete I/O DefinitionTable B.1LSM Data Table ListTable NameNumber of ParametersID/Numberof WordsType of TableFacto

Strany 45 - = frequency in floating point

A–BPreface iUsing This ManualReview the table below to familiarize yourself with the topics contained inthis manual.For information about: Refer to ch

Strany 46

Appendix BBlock Transfer and DiscreteI/O DefinitionB–2Table B.2Factory Configuration ParametersParameterNumberWordNum-berDescription Range Modulus 1 –

Strany 47 - Catalog Number Explanation

I/O DefinitionAppendix BBlock Transfer and DiscreteB–3Table B.2Factory Configuration Parameters (Continued)ParameterNumberWord Number Description Rang

Strany 48 - Appendix

Appendix BBlock Transfer and DiscreteI/O DefinitionB–4Table B.3User Configuration ParametersParameterNumberWordNumberDescription Range Modulus11 Deman

Strany 49

I/O DefinitionAppendix BBlock Transfer and DiscreteB–5Table B.4Acknowledge Factory Configuration ParametersParameterNumberWordNumberDescription Range

Strany 50

Appendix BBlock Transfer and DiscreteI/O DefinitionB–6Table B.5Acknowledge User Configuration ParametersParameterNumberWordNumberDescription Range Mod

Strany 51

I/O DefinitionAppendix BBlock Transfer and DiscreteB–7Table B.6Synchronizing Bus Error ParametersParameterNumberWordNumberDescription Range Modulus1 1

Strany 52

Appendix BBlock Transfer and DiscreteI/O DefinitionB–8Table B.7Synchronizing Bus Voltage/Current ParametersParameterNumberWordNumberDescription Range

Strany 53

I/O DefinitionAppendix BBlock Transfer and DiscreteB–9Table B.7Synchronizing Bus Voltage/Current Parameters (Continued)ParameterNumberWordNumberDescri

Strany 54

Appendix BBlock Transfer and DiscreteI/O DefinitionB–10Table B.8Synchronizing Bus Power ParametersParameterNumberWordNumberDescription Range Modulus1

Strany 55

I/O DefinitionAppendix BBlock Transfer and DiscreteB–11Table B.8Synchronizing Bus Power Parameters (Continued)ParameterNumberWordNumberDescription Ran

Strany 56

PrefaceUsing This Manual iiIn this manual, the following terms and conventions are used:Abbreviation TermAWG American Wire GageBTR Block Transfer Read

Strany 57

Appendix BBlock Transfer and DiscreteI/O DefinitionB–12Table B.9Reference Bus Voltage ParametersParameterNumberWordNumberDescription Range Modulus1 1V

Strany 58

I/O DefinitionAppendix BBlock Transfer and DiscreteB–13Table B.10Control Request ParametersParameterNumberWordNumberDescriptionRangeIndividualBitsModu

Strany 59

Appendix BBlock Transfer and DiscreteI/O DefinitionB–14Table B.11Diagnostic ParametersParameterNumberWordNumberDescription Range Modulus1 1 0 – 999

Strany 60

I/O DefinitionAppendix BBlock Transfer and DiscreteB–15Table B.11Diagnostic Parameters (Continued)ParameterNumberWordNumberDescription Range Modulus A

Strany 61

Appendix BBlock Transfer and DiscreteI/O DefinitionB–16Table B.11Diagnostic Parameters (Continued)ParameterNumberWordNumberDescription Range Modulus18

Strany 62

I/O DefinitionAppendix BBlock Transfer and DiscreteB–17Table B.13Discrete Input/Output DataDecimalBit NumberOctal BitNumberDiscrete Output(from Proces

Strany 63

Appendix BBlock Transfer and DiscreteI/O DefinitionB–18

Strany 64

A–BCAppendixC–1Sample Ladder ListingThis is a sample ladder. It shows a way to configure the block transfers forthe 1402–LSM and the Power I/O Config

Strany 65

Appendix CSample Ladder ListingC–2Rung 2:2 The trigger must be present and the run sequence must be complete for the config mode to be enabled.

Strany 66 - I/O Definition

Appendix CSample Ladder ListingC–3Rung 2:5 Resets configuration mode sequencer when in the run mode.| Config

Strany 67 - Sample Ladder Listing

A–B1Chapter1–1Product DescriptionAfter reading this chapter, you should be able to identify the product featuresand system applications.The Bulletin 1

Strany 68 - Appendix C

Appendix CSample Ladder ListingC–4Rung 2:8 Sequence through pre–selected block transfers when the active block transfer has completed or has enc

Strany 69

Appendix CSample Ladder ListingC–5Rung 2:11 Perform BTR User Configuration Parameters.| Us

Strany 70

Appendix CSample Ladder ListingC–6Rung 2:14 Perform BTR Synchronizing Bus Error Parameters.|

Strany 71

Appendix CSample Ladder ListingC–7Rung 2:17 Perform BTR Reference Bus Voltage Parameters.|

Strany 72

Appendix CSample Ladder ListingC–8Rung 2:20 Perform BTW for User Configuration Parameters.|

Strany 73

Appendix CSample Ladder ListingC–9Rung 2:23 Configuration data is valid and the sequence is complete.|

Strany 74

Appendix CSample Ladder ListingC–10

Strany 75

DAppendixD–1Line Synchronization ModuleMechanical DimensionsFigure 1Dimensions for Line Synchronization Module1.57( .06 )6.73( .27 )31.72( 1.25 )62.2

Strany 76

Appendix DMechanical DimensionsD–2

Strany 77 - Mechanical Dimensions

A–BAppendixEE–1Bulletin 1402 Technical SpecificationsINPUTS:Current 0 to 5A RMS Cont., 200A RMS 1 SecondFrequency 40 to 100 Hz (steady-state)Dielectri

Strany 78 - Appendix D

Chapter 1Product Description1–2In order to synchronize two three phase systems without high instantaneousenergy transfer, the voltage, frequency, and

Strany 79

Appendix ETechnical SpecificationsE–2CSA certifies products for general use as well as for use in hazardouslocations. Actual CSA certification is ind

Strany 80 - CODE T3C

Appendix EPower Monitoring E–3La CSA certifie les produits d’utilisation générale aussi bien que ceux quis’utilisent dans des emplacements. La certifi

Strany 81 - Approbation d’utilisation

Appendix ETechnical SpecificationsE–4If this product has the CE mark it is approved for installation within theEuropean Union and EEA regions. It has

Strany 86

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improveproductivity and quality for more than 90 years. We design, manuf

Strany 87 - Worldwide representation

Chapter 1Product Description1–3In addition to the synchronization function, the LSM provides an extensivearray of monitoring information for systems w