Chapter 3
Configuration & Interfacing
3–8
Overflow Control (Par # 517) – This parameter determines what action
the Drive will take when a Block Output value overflow condition occurs.
Refer to Table 3–E for details.
BIT
0
0
1
1
Table
3-E.
Function Block Overflow Control, Parameter 517
Send last state (Default)
Zero Inputs
Send max value, pos or neg
None
Action Taken
11 10
0
1
0
1
Overflow
Action
BIT
0
0
1
1
None (Default)
Warning
Soft
Hard
Fault Type
3 2
0
1
0
1
Overflow
fault Severity
IMPORTANT: Refer to Chapter 6 for definition of Fault types before
attempting configuration or Start-up.