Publication 1394-IN024B-EN-P — February 2004
1-14 Commissioning Your 1394 SERCOS Interface System
5. Select Data Rate, Cycle Time, and Optical Power settings.
Ensure the Data Rate setting matches DIP switches 2 and 3
(baud rate) as set on the system module, or use the Auto
Detect setting.
Set the Cycle Time according to the table below.
Ensure the Optical Power setting (high or low) matches DIP
switch 1 as set on the system module.
6. Select Finish. Your new module appears under the I/O
Configuration folder in the explorer window.
7. Repeat steps 1-6 for each Logix module.
Logix SERCOS
Module
1394 SERCOS interface
System Module Series
Data
Rate
Mbit/s
SERCOS Ring
Cycle Time
ms
Number
of Axes
1756-M08SE
(Series A)
C or D 4
0.5 N/A
1.0 up to 4
2.0 up to 8
1756-M08SE
(Series B)
D only 8
0.5 N/A
1.0
up to 8
2.0
1756-M16SE or
1784-PM16SE
C or D 4
0.5 N/A
1.0 up to 4
2.0 up to 8
D only 8
0.5 N/A
1.0 up to 8
2.0 up to 16