Rockwell-automation 1305 AC Drive, Firmware 1.01-3.00 User Manual Uživatelský manuál Strana 114

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 162
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 113
Chapter 5 –Programming
5-46
Owners Group (cont.)
[S
t
ar
t
O
w
ner
]
Parameter # 104
[S
t
ar
t
O
w
ner
]
Parameter Type Read Only
This parameter displays which adapters are currently
issuing Start commands. Since Start commands are edge
triggered, multiple adapters can issue the Start command
simultaneously and as such are displayed. However, it is
the first low to high transition of the Start (once all Stops
and/or Faults are removed) that initiates the actual Start
command.
Units Byte Settings 1
0
Controlling
Not Controlling
[
J
o
g
O
w
ner
]
Parameter # 105
[
J
o
g
O
w
ner
]
Parameter Type Read Only
This parameter displays which adapters are currently
issuing JOG commands. Since the JOG function is
momentary, multiple adapters can issue Jog commands
simultaneously. This means that all adapters issuing the
JOG must stop commanding the JOG before the function
ceases. IMPORTANT: Stop commands will terminate JOG
control and Start commands will override any JOG
command.
Units Byte Settings 1
0
Controlling
Not Controlling
Zobrazit stránku 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 161 162

Komentáře k této Příručce

Žádné komentáře