4-6 Troubleshooting
PowerFlex 1203-USB Converter User Manual
Publication DRIVES-UM001D-EN-P
Converter Events
Many events in the event queue occur under normal operation. If you
encounter unexpected communication problems, the events may help you or
Allen-Bradley personnel troubleshoot the problem. Converter events can be
viewed with Connected Components Workbench software, version 1.02 or
later.
Event Codes for DPI Drives
Code Events Description
1 No Event No event present in the event queue.
2 DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be caused by
loose or broken cables, or by noise.
3 Ping Time Flt A ping message was not received on DPI within the specified time.
4 Port ID Flt The converter is not connected to a correct port on a DPI drive.
5 Port Change Flt The DPI port changed.
6 Host Sent Reset The DPI drive issued this because it was reset.
7 EEPROM Sum Flt The EEPROM in the converter is corrupt.
8 Online @ 125kbps The converter and DPI drive are communicating at 125kbps.
9 Online @ 500kbps The converter and DPI drive are communicating at 500kbps.
10 Bad Host Flt
11 Dup Port Flt Another peripheral with the same port number is already in use.
12 Type 0 Login The converter has logged in for type 0 control.
13 Type 0 Time Flt The converter has not received a type 0 status message within the
specified time.
14 DL Login
15 DL Reject Flt
16 DL Time Flt
17 Reserved
18 Control Disabled The converter has sent a ‘Soft Control Disable’ command to the DPI
drive.
19 Control Enabled The converter has sent a ‘Soft Control Enable’ command to the DPI
drive.
20 PCCC I/O Time Flt The converter has not received a PCCC Control message for longer
than the specified PCCC Control Time-out.
21 Normal Startup The converter initially powered up or was reset.
22 Message Timeout The DPI drive did not respond to a message request. Verify that cabling
is correct.
23 Ping in Message An unexpected ping was received.
24 DPI Fault Msg The drive entered a faulted state.
25 DPI Fault Clear A DPI drive has issued a fault clear message.
26 Manual Reset