2.0 MECHANICAL/ELECTRICALDESCRIPTION 2.1 Mech
2Ć2GNDFuse Type250V MDQ24 VDC:Use 0.75A120 VAC:Use 0.25ADC-DC+L2L124VDC120VACInput PowerAnalog I/OModeInputAnalog Rail61C3500 to 10V IN/OUTPWROKCOMOK
2Ć3The faceplate of the module contains three electrical connectorslabeled Input", Analog I/O", and Input Power" (reading top tobott
2Ć4DACIĆOUTRFB+15V+VĆOUT-VĆCOMMON10KFigure 2.2 Ć Typical Output Circuit to A/DconverterVĆINVĆOUT90K90KFigure 2.3 Ć Typical Input CircuitThe Analog Ra
3Ć13.0 INSTALLATIONThis section describes how to install and replace the Analog Railmodule. Note that analog signals are sensitive to variations intem
3Ć2 Use the following procedure to install the Analog Rail module.Step 1. Using the mounting dimensions shown in figure 3.1,pre
3Ć3Step 2. If the power supply you are using is 24 VDC, replace thefactoryĆinstalled .25A fuse with the .75A fuse that came inthe shipping box with th
3Ć4 0 123VĆOUTCommon(no label)0Ć10V+ outputcommon(shield; no connection)*1 456VĆOUTCommon(no label)0Ć10V+ out
3Ć5Channel 0Channel 1Channel 2Channel 3-+LoadVĆOutCommon123-+LoadVĆOutCommon456+-SourceVĆInCommon789+-SourceVĆInCommon101112Figure 3.2 Ć Typical R
#"% #"" !" " ! " ''& "! !#!
3Ć6WARNINGBE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NOUNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THISPRECAUTION COULD RESUL
3Ć7Take the .25A fuse out of the fuse holder and replace itwith the .75A fuse. ReĆinsert the fuse holder into themodule. Turn the screwdriver clockwis
3Ć8For DCS 5000, AutoMax, or Distributed Power DĆC Drivesystems, use the DCS 5000 or AutoMax ProgrammingExecutive software I/O Monitor function, respe
4Ć1 This section describes how the data is organized in the module andprovides examples of how the module is accessed by applicationprog
4Ć2 Configuration is the process of describing in software how thehardware a
4Ć3Analog Rail Module Connected Directly to AutoMate 30 or 40(Local Head Mode or Rail Mode)The following sample configuration shows two Analog Rail mo
4Ć4Analog Rail Module Connected to AutoMate 30 or 40 Through a Local I/O Head(Rail Mode Only)The following sample configuration shows two Analog Rail
4Ć5Analog Rail Module with AutoMate Local I/O Processor (Local Head Mode Only)The following sample configuration shows three Analog Rail modules conne
4Ć6Analog Rail Module with AutoMate Remote I/O Head (Local Head Mode Only)The following sample configuration shows one Analog Rail module connected to
4Ć717 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0Octal12 bits of converted analog dataoverĆrange (1=overĆrange)underĆrange (1=underĆrange)channel being read:
ITable of Contents1.0 Introduction 1Ć1...1.1 Additional Information 1Ć1...
4Ć8 In Local Head mode, the module is imaged in four I/O registers ofthe processor. Data from all four cha
4Ć94.1.4 Analog In (AIN) and Analog Out (AOUT) InstructionBlocksThe AIN and AOUT blocks are used, respectively, to read inputsfrom and write outputs t
4Ć10AOUT Instruction BlockThe example below shows an AOUT block for an Analog Rail module connectedto port 2 of a local I/O head, which in turn is con
4Ć11For DCS 5000 or AutoMax Version 2.1 or earlier, use the RIODEFstatement to define each channel on the Analog Rail module as aseparate register. No
4Ć12The value in the channel defined as CHANNEL_2 is eitheroverĆrange or underĆrange:10000 RANGE_ERROR@ = CHANNEL_2 AND 3000HThe value in the channel
5Ć15.0 DIAGNOSTICS ANDTROUBLESHOOTINGDANGERTHE REMAINING STEPS ARE MADE WITH POWER ON. EXERCISE EXTREMECAUTION BECAUSE HAZARDOUS VOLTAGE EXISTS. FAILU
5Ć2DANGERDO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS POWERON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW TERMINALS.ALWAYS TURN OFF POW
5Ć3DANGERVOLTAGE IS PRESENT ON THE PLUG CONNECTOR TERMINALS. DISCONNECTTHE POWER AT THE SOURCE BEFORE TOUCHING THE PLUG CONNECTORTERMINALS. FAILURE TO
5Ć4Step 3. Try to clear the condition by disconnecting and thenreĆconnecting the I/O Rail cable. Make certain theconnections are tight. If applicable,
AĆ1# D Storage temperature: -40_Cto85_C-40_Fto185_FD Operating temperature at the module: 0_Cto60_C32
II Technical Specifications AĆ1... Block Diagram BĆ1...
AĆ2 D Operating range: 0 Ć 10 VDCD Number of channels: 2 (singleĆended)D Number of commons: 1 (shared among all 4 ch
BĆ1 D/A CONTROL SIGNALSDATA BUSA/D CONTROLSIGNALDATA BUSLOCAL HEAD OR RAIL MODE SWITCHSERIAL HOST INTERFACEHOSTINTERFACECIRCUITR
fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsaafdfdsfdsfdfdsfdsfsadfdaasfdfaddfdd
CĆ1 The following AutoMate program sequences can be used to interface to anAutoMate Processor that does not support th
CĆ2 At the End of the ScanIf counter = 0, MOVE register 40 to register 0 for output.Ă44.01[Ă/Ă]Ă44.00[Ă/Ă]Ă45.00(ăă)EN MOVE ENLENG
CĆ3 Increment counter 0, 1, 2, 3 and then back to 0, and so on.Ă45.04(ăă)EN ADD ENLENGTH: 1SRC: 44SCR 2: k1DEST: 44Ă76.00(ăă)Ă45.0
fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsaafdfdsfdsfdfdsfdsfsadfdaasfdfaddfdd
fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsaafdfdsfdsfdfdsfdsfsadfdaasfdfaddfdd
For additional information1 Allen-Bradley DriveMayfield Heights, Ohio 44124 USATel: (800) 241-2886 or (440) 646-3599http://www.reliance.com/automaxCop
III Figure 1.1 Ć Analog Rail Module Hardware Configuration 1Ć3...Figure 2.1 Ć Analog Rail Module Faceplate 2Ć2...
fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsaafdfdsfdsfdfdsfdsfsadfdaasfdfaddfdd
1Ć11.0 INTRODUCTIONThe products described in this instruction manual are manufacturedby Reliance Electric Industrial Company.The 2ĆIn/2ĆOut 0Ć10 Volt
1Ć2 JĆ3120 AutoMate 20 USER'S MANUAL JĆ3141 AutoMate 40 CONTROL PROCESSOR INSTRUCTIONMANUAL JĆ3150 AutoMate 30/40 SOFTWARE REFERENCE MANUAL J
1Ć3The Analog Rail module can be configured with the hardware(purchased separately) listed in figure 1.1. DCS 5000/AutoMaxRemot