Installing Block I/O
Chapter 3
3-3
Maximum
Network Distance
Baud Rate
Used
Maximum CapacityandWhen using
16 blocks/channel, 32
blocks/scanner, (128 blocks with 4
57.6K 10,000 cablefeet
PLC 5 f il ( ti d)
PL
C
5/
2
50
 re
q
uires
blocks/scanner
,
(128
blocks
with
4
scanners) with 150 ohm terminator
and extended node addressing
115.2K 5,000 cablefeet
PLC5 family (continued)
PLC
5/250
 requ
i
res
a 5150RS remote scanner
32 blocks/channel, 32
57.6K 10,000 cablefeet
32
blocks/channel
,
32
blocks/scanner, (128 blocks with 4
scanners) with 82 ohm terminator
115.2K 5,000 cablefeet
scanners)
with
82
ohm
terminator
and extended node addressing
230.4K 2,500 cablefeet
SC / SC /
S/OS
16 blocks with 150 ohm terminator
57.6K 10,000 cablefeet
SLC5/02 or SLC5/03
Controllers
1747SN Remote I/O Scanner
Module
16
bl
oc
k
s w
i
t
h
1
5
0
o
h
m term
i
nator
115.2K 5,000 cablefeet
Controllers
Module
16 blocks with 82 ohm terminator 230.4K 2,500 cablefeet
1
PLC5/15 series A and PLC5/15 series B prior to revision H (B/H) can only address 3 blocks.
2
PLC5/25 revisions prior to A/D can only address 7 blocks.
Figure 3.1 shows the mounting dimensions for the block I/O module.
Mount the blocks vertically with a minimum of 2” between blocks. This air
gap is necessary to maintain proper cooling air flow through the block.
Figure 3.1
Mounting
Dimensions for the Block I/O Modules
2
Mounting Holes
for 1/4inch screws
1
30
2.710
(68.8)
1.71
(43.4)
17918AC
6.95
(176.5)
120V
ac IN/OUT
6.60
(167.6)
INPUT OUTPUT
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
0.5
(12.7)
6.95H
x 2.710W x 3.85D
(176.5H x 68.8W x 98D)
Inches
(Millimeters)
CAUTION:
When tightening grounding
stud nut, do not exceed 15 inlbs.
2.0
(50.8) air gap
on all 4 sides.
Block
Operating temperature in
air
gap
below module must
not
exceed 60
o
C (140
o
F).
ALLENBRADLEY
Dimensions
1
30
4.35
(110.5)
3.35
(85.1)
6.95
(176.5)
6.60
(167.6)
0.5
(12.7)
179124B8
24V
dc IN/OUT
IN OUT
00
01
02
03
04
05
06
07
30
1
RACK
#
ALLENBRADLEY
10
11
12
13
14
15
16
17
00
01
02
03
04
05
06
07
G
G+1
00
01
02
03
04
05
06
07
IN G
IN (G+1)
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
OUT G
G
IN
00
01
02
03
04
05
06
07
COMM
STATUS
00
01
02
03
04
05
06
07
Equipment
Grounding
Stud
6.95H
x 4.35W x 3.85D
(176.5H x 1
10.5W x 98D)
16point Block I/O Modules
32point Block I/O Modules
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
Installing the Block I/O